Custom Air Products and Services' New Industrial Grade Wall Mount Air Conditioning Unit
- The unit's casing is fabricated from 16 gauge galvanized paint grip.
- Access doors are fabricated from 18 gauge galvanized paint grip and insulated with 1" insulation for sound and condensate control.
- All surfaces subject to condensation are insulated with 1" insulation.
- Two (2) Copeland scroll compressors. Each compressor circuit shall have the following:
- Auto reset low pressure switch
- Auto reset high pressure switch
- Isolation valves liquid line filter dryer
- Thermostatic expansion valves
- High limit safety for heater elements
- 1 minute time delay between compressors turning on
- Liquid line filter dryer
- Sight glass
- One (1) dual circuit evaporator coil.
- One (1) dual circuit condenser coil.
- Twin DWDI forward curved fans.
- TEFC evaporator fan motor.
- Direct drive condenser fan with TEFC motor.
- Electric heater with thermal cutouts.
- 304 stainless steel drain pan.
- Control panel with the following features:
- Instrument transformer, 460-24 VAC with secondary circuit breaker
- Condenser fan motor contractor with thermal overload
- Evaporator fan contractor with thermal overload
- Electric heater contractor(s)
- Two (2) compressor contractors
- ACmax ETCLO-830 safety controller with the following features:
- Microprocessor based controller
- Random start of 0-60 seconds to avoid simultaneous start of several units after power interruption
- Anti-short cycle timer delay (0,3,5 or 10 minutes)
- Time delay of 30 seconds between the two compressors
- Built-in automatic warning flag setting to monitor the fault for a period of 30 minutes from the first fault signal
- Manual and automatic setting for compressor rotation
- TRIAC output fault for alarm signal
- LED status indicators (power and fault)
- The units will be tested and witnessed at our facility at full load conditions to verify proper operation prior to shipment
Options
- Hot gas bypass for capacity control (one or both circuits)
- Main circuit breaker
- Corrosion resistant coatings
- Stainless steel casing
- Copper / Copper coils
- Hazardous area construction
Electrical Data
Model
IWM7.5A
IWM10A Electrical
460/3/60
460/3/60 Amps - Cooling
20.2MCA
25.5 MCA Amps - Heating
9 kW - 16.5 MCA
15 kW - 25.3 MCA Amps - Compressor
2 @ 7.4RLA
2@10.9RLA Amps - Evap
1½ HP, 2.2 FLA
2HP, 2.8FLA Amps - Cond
1½ HP, 2.7 FLA
2HP, 3.3FLA MOCP
25
30
IWM7.5A
IWM10A Electrical
460/3/60
460/3/60 Amps - Cooling
20.2MCA
25.5 MCA Amps - Heating
9 kW - 16.5 MCA
15 kW - 25.3 MCA Amps - Compressor
2 @ 7.4RLA
2@10.9RLA Amps - Evap
1½ HP, 2.2 FLA
2HP, 2.8FLA Amps - Cond
1½ HP, 2.7 FLA
2HP, 3.3FLA MOCP
25
30